THERE ARE 2 STYLES OF INSTALLATION
CEILING TYPE
FLOOR TYPE
Each type is similar to the other as follows; determine the
mounting position on ceiling or wall by using paper
pattern to indicate indoor frame. Mark the pattern and
pull out the paper pattern. Remove the return grill, the
side panel and the hanger bracket from the indoor unit as
per procedure below.
Press the fixing knob of the return grilles, the grilles
will be opened wider and then pull it out from the
indoor.
Remove the side panel fixing screw and pull to the
front direction (arrow direction) to remove (Refer to
Fig.24).
Loosen two hanger bracket setting bolts (M8) on each
side for less than 10mm. Remove two hanger bracket
fixing bolts (M6) on the rear side. Detach the hanger
bracket by pulling it backward (Refer to Fig.26).
Set the suspension bolt.(Use W3/8 or M10 size
suspension bolts).
Adjust the distance from the unit to the ceiling slab
beforehand (Refer to Fig.25). Fix the hanger bracket to
the suspension bolt.
WARNING
Make sure that extended suspension bolt from the
ceiling stays inside the arrowed position. Readjust the
hanger bracket when it is outside the arrowed position
(Refer to fig. 27).
Suspension bolt stays inside the cap of indoor unit.
Never remove the cap.
Lift the unit and slide forward unit the dent. (Refer to
fig. 28).
Screw tightly both hanger bracket settings bolts (M8)
(refer to fig. 26).
Screw tightly both hanger bracket fixing bolts (M6) to
prevent the movement of the indoor unit. (refer to
fig. 26).
Adjust the unit height so that rear side of the drain pipe
slightly inclines to improve drainage.
CAUTION
Adjust the height by turning the nut with a spanner.
Insert the spanner from the hanger bracket opening
(refer to fig. 29).
In case of hanging
It is possible to install using inward facing hanger brackets
by not removing the brackets from indoor unit (refer to
fig. 30). Be sure to use only the specified accessories and
parts for installation work.
Side panel fixing screws (M4)
Fig. 24
Fig. 25
Ceiling
40 mm
or less
Suspension bolt
Hanger bracket
Fig. 26
Hanger bracket
Hanger bracket setting
bolt (M8)
Hanger bracket fixing
bolt (M6)
Ceiling slab
Bolt position
inward
Hanger bracket
Fig. 27
Fig. 28
Fig. 29
Fig. 30